Sustainability Sustainability

Information about PCB

About the issue of PCB

New production, use were canceled in 1972 by administrative advice (afterwards laws and regulations) of the Ministry of International Trade and Industry, but PCB pollution of around dozens of mg/kg was confirmed in the electric apparatuses made after that and, about PCB, was announced in 2002. It becomes clear that a very small amount of PCB mixture being extensive pollution to be started from use of reproduction insulating oil, pollution cause last for the life cycle whole of insulating oil according to "a very small amount of PCB pollution cause investigation report" of low-concentrated PCB pollutant measures Exploratory Committee installed by Ministry of Economy, Trade and Industry, Ministry of the Environment (May 10, 2004 announcement), and plural number exists. Our company does not produce transformers using PCB oil, but, also, cannot judge PCB component from model, tablet without being able to deny possibility of a very small amount of PCB mixture in at the time of transportation at the time of insulating oil production even if it is electric apparatuses which we aim at PCB and do not use.

We heard PCB analysis in insulating oil.

PCB is not contained in us by insulating oil, or please feel free to contact in analysis, one which you can judge in occasion of facilities update and the disposal. Please confirm "PCB analysis out of insulating oil" in detail.

※Because we can judge from "kikimeiban" about highly-concentrated use PCB electric apparatuses, analysis of highly-concentrated PCB is not accepted.

About transformer which cannot deny possibility of a very small amount of PCB mixture

01.With a very small amount of PCB mixture transformer

A very small amount of PCB mixture transformer was not originally oil transformer using PCB intentionally, but we said transformer considered that a very small amount of PCB got mixed with insulating oil in at the time of insulating oil production, transportation and became clear in 2002. About findings about a very small amount of PCB mixture to transformer made in us, please see the following.

02.Our opinion about a very small amount of PCB mixture

Because we do not handle PCB oil and reproduction oil from the beginning of transformer production, we judge that there is not possibility of a very small amount of PCB mixture in process of manufacture, but cannot deny possibility of PCB mixture not to intend. We do the following with we opinion about very small amount PCB mixture presence based on management (we confirm PCB-free existence) being doing transformer process of manufacture appropriately in thing, after 1990 when we did not carry out PCB-free confirmation in insulating oil before 1989.

  • It is oil transformer of production before 1989: We cannot deny possibility of PCB mixture.
  • It is oil transformer of production after 1990: There is no PCB mixture in our shipment stage.
03.Matter which wants you to be careful about customers
  • We have you analyze oil immediately at stage when transformer owning finished use in any of "the transformer which cannot deny possibility of a very small amount of PCB mixture", and it is necessary to confirm whether it is transformer of very small amount PCB mixture. (note 1)

    Judgment (note 2) by analysis of oil

    • When level of polychlorinated biphenyl exceeds 0.5 mg/kg: We correspond to a very small amount of PCB mixture transformer.
    • When levels of polychlorinated biphenyl are 0.5 mg/kg or less: We do not correspond to a very small amount of PCB mixture transformer.
  • When a very small amount of PCB mixture becomes clear in used transformer, report is necessary for Manager Director Ministry of Economy, Trade and Industry Nuclear and Industrial Safety Agency industry preservation to have jurisdiction over place setting up by "electric report rule based on Electricity Enterprises Law concerned".
  • Appropriate storage (note 3) is necessary till we perform report (prefectural governors or the cabinet ordinance mayor) by "special measures law (PCB special measures law) about promotion of appropriate processing of polychlorinated biphenyl waste" when we finish use of transformer that used a very small amount of PCB mixture became clear and process.
  • When a very small amount of PCB mixture becomes clear, we perform report (prefectural governors or the cabinet ordinance mayor) by "special measures law (PCB special measures law) about promotion of appropriate disposal of polychlorinated biphenyl waste", and storage (note 3) that is appropriate till it processes is necessary for transformer keeping.
  • A very small amount of (low concentration) PCB waste has a duty to complete processing by March 31, 2027. As disposal of a very small amount of PCB mixture transformers was had start (note 4) of, I would like appropriate processing within period.

Flow (figure of flow) of distinction method and correspondence of a very small amount of PCB mixture transformer

March 30, 2012

※Tablet mention company name: Before September, 2001 "Kyushu Transformer"

※Tablet mention company name: After October, 2001 "KYUHEN"

※1.Please confirm "about transformer which cannot deny possibility of a very small amount of PCB mixture".

  • A

    Occupied

    • It is available sequentially
    • It is reported to Manager Director Ministry of Economy, Trade and Industry industrial preservation by Electricity Enterprises Law/Electric-related report rule
    • We handle based on disposal method of a very small amount of (low concentration) PCB mixture transformer by deadline for processing (March 31, 2027)
  • B

    We are going to discard

    • We are reported for prefectural governors or the cabinet ordinance mayor by PCB special measures law
    • We handle based on disposal method of a very small amount of (low concentration) PCB mixture transformer by deadline for processing (March 31, 2027)
    More details are here
  • C

    Occupied

    • It is available sequentially
      (we handle as a very small amount of PCB mixture transformer equally)
  • D

    We are going to discard

    • We carry out level of polychlorinated biphenyl analysis (cf. G) immediately at stage when we finished use

    [as a result of analysis]
    In the case of 0.5km/k excess: We correspond to B
    When it is 0.5km/k or less: We correspond to F

  • E

    Occupied

    • It is available sequentially
    • The handling is possible as transformer which does not include PCB
  • F

    Industrial plan

    • We can discard as industrial waste
  • G

    About PCB analysis

    Please confirm "PCB analysis out of insulating oil" about PCB analysis (our Environnental Analysis Center).

  • H

    Customer inquiry counter

    After confirming the product name, the production year, manufacturing number when you cannot judge oil transformer or you will not know, I would like inquiry in "customer inquiry counter".

About storage of transformer which cannot deny possibility of a very small amount of PCB mixture

01.About the handling of used transformer

We can just use thing currently using sequentially. In any of the transformer (use of PCB transformer, transformer that a very small amount of PCB mixture was confirmed) that used apparatus contains PCB, you have Manager Director Ministry of Economy, Trade and Industry atomic energy security industry preservation report by electric report rule based on "Electricity Enterprises Law" concerned, and you follow so that malfunction such as leak oil does not occur, and please carry out check every day. In addition, it is forbidden using newly when PCB component dismantles confirmed apparatus from electric circuit.

02.About storage

When you remove transformer that mixture of use of PCB transformer, very small amount PCB was confirmed from electric circuit and keep, please follow as follows. In addition, it is necessary appropriate to handle that it followed as follows when we keep thing which cannot deny possibility of PCB mixture. ("2: Paragraph 2 of Article 12 method of waste disposal" ": 13 of Article 8, 2 Paragraph 3 of 2 of Article 8 the method of waste disposal enforcement regulations" ": Ministry of International Trade and Industry Machinery and Information Industries Bureau electric apparatus section in July, 2000 about the handling of use of PCB electric apparatus")
When we keep, other than method of waste disposal, I would like the handling according to the next instructions.

  • 1) Identifiably display

    We display next and distinguish from general apparatus
    Indication (indication of being apparatus which or cannot deny possibility of a very small amount of PCB mixture) of being apparatus that use of PCB, a very small amount of PCB mixture were confirmed

    • Amount (the number, mass, capacity)
    • Indication (full name, contact information) of administrator
    • The year when we started storage
    • Processing completion time limit [we show we handle by) in the case of (low concentration PCB waste on March 31, 2027]
    • Reference (contact information such as maker names) of apparatus
    • As for the thing which handled legal procedure of "method of waste disposal" "Electricity Enterprises Law" either, it is displayed it
  • 2) Isolation of apparatus

    We isolate so that we distinguish target apparatus from general, disposing, and insulating oil in the apparatus concerned is scattered and flows out and penetrates underground and bad smell does not display and keep. In addition, we establish partition so that other than manager for storage and manager cannot approach apparatus.

  • 3) Measures of leak oil prevention

    When it is to thing keeping, we receive in strong container produced with storing to container which we sealed up, materials which are hard to penetrate and prevent leak caused by corrosion from getting up.

  • 4) Measures of fire prevention

    When we keep designated amount (as for the fourth kind third oil 2,000 liters) or more insulating oil, we obey technical standards such as position, structure, facilities of storage area according to the Fire Services Act.

  • 5) Check

    We check apparatus keeping regularly and try for prevention such as pollution or loss by leaks. In addition, record check result; and of apparatus keep until disposing is completed.

  • 6) Others

    When we dispose, we provide information about property, quantity of contents in trust and dispose by processing technology authorized legally.

03.About attention in maintenance (absorbent paper handling work by oil exchange, lubrication)
  • 1) In the case of transformer with apparatus that a very small amount of PCB mixture was confirmed and the possibility

    When we maintain, we would like the handling such as electric insulating oil used for apparatus as follows.

    • Oil which we pulled out by oil exchange work can enter container which we sealed up and keeps according to "about the storage" mentioned above.
    • We record consumption, maker, standard of oil, work day that oiled, and oil which we supplemented newly keeps. In addition, oil to supplement newly obtains PCB-free certificate from oil manufacturer beforehand.
    • We keep tools for appliance, waste, rubber gloves which we used for extraction work of oil and polluted protection according to "about the storage" mentioned above. In addition, we treat about case to include oil which we pulled out for investigation equally.
  • 2) In the case of use of PCB transformer

    Please do not perform oil exchange work to make nonproliferation and detoxification handling of pollution difficult.

About the related law

The handling that followed law that is currently using and stop planned electric apparatus warns use enough in application (regulation) of law varying according to the situation of transformer and is related, please.

When a very small amount of PCB mixture transformer is confirmed use of PCB transformer, law ※3 ※Report according to 4 is necessary. When apparatus currently using is available continuously, but remove from electric circuit once, newly to electric circuit cannot be connected (※ 5).

In addition, about highly-concentrated use of PCB electricity workpiece and PCB waste, deadline for disposal every area of notification (prohibition of provisional measure of continuously using, disposal in period) is announced, and disposal in period when we followed law (※ 1 ※ 3 ※ 5) is necessary. Please see new regulation "of use of PCB electricity workpiece of" high density.

When a very small amount of PCB mixture is not confirmed, we do not receive application of law (※ 3) and can handle (0.5 mg/kg or less) as industrial waste at the time of the disposal. In addition, about apparatus said to that we cannot completely deny possibility of PCB mixture, processing that is appropriate like PCB waste is necessary till it is confirmed not to contain PCB.

The related law

※1.2 Paragraph 2 of "law about disposal of waste and cleaning" (revision last on June 14, 2019) Article 12

※2.13 of 2 Paragraph 3 Article 8 of 2 of "law enforcement regulations about disposal of waste and cleaning" (revision last on September 4, 2019) Article 8

※3."Special measures law about promotion of appropriate disposal of polychlorinated biphenyl waste" (revision last on May 2, 2016) Article 8, Article 10

※4.Paragraph 2 of "electric report rule concerned" (revision last on July 1, 2019) Article 4

※5."Departmental order to determine technical standard about electric equipment" (revision last on March 31, 2017) Chapter 1 basic rule Section 4 (prevention such as pollution) Article 19 14, supplementary provisions Paragraph 2

New regulation of use of highly-concentrated PCB electricity workpiece

Disposal in period of highly-concentrated PCB waste was decided in occupied time limit of use of highly-concentrated PCB electricity workpiece by laws and ordinances revision.

Departmental order (14, supplementary provisions Paragraph 2 of Article 19) to determine technical standard about electric equipment
Conventional regulation, continuation and addition ※Underline part

Electricity machine appliance using insulating oil including polychlorinated biphenyl and electric wire (OF cable) must not provide equipment 14 of Article 19 in electric circuit.

Revision

Departmental order supplementary provisions Paragraph 2: It is the ban on use for each area of notification from the next day of time limit (note) of notification

(note) time limit every area of notification: For disposal of use of PCB product and PCB waste in time limit (Ministry of the Environment, Ministry of Economy, Trade and Industry)

  • Kitakyusyu business area: Until transformer, condenser March 31, 2018
  • Kitakyusyu, Osaka, Toyota business area: Until March 31, 2021 such as stabilizer and pollutant (the end of the disposal period)

As for the above, the use of highly-concentrated PCB electricity workpiece in Kitakyusyu business area, provisional measure (use of old trade and industry departmental order No. 70 continuation) is prohibited from (April 1) on the next day of March 31, 2018, and 14 of departmental order Article 19 is applied. It is made regulation (electric report rule abolition report of relationships, PCB special measures law report) as PCB waste afterward.

※ You have each manufacturer confirm, or please refer to homepage of Japan Electrical Manufacturers' Association for "electric workpiece using highly-concentrated PCB".

PCB analysis out of insulating oil

We have many results about PCB analysis in insulating oil in KYUHEN.

About abolished electric apparatus with a very small amount of PCB blend

About apparatus which a very small amount of PCB may get mixed or cannot deny, it is necessary to actually measure level of polychlorinated biphenyl in insulating oil, and to judge presence of component at stage when we finished use.

We handle as existence (level of polychlorinated biphenyl: 0.5 mg/kg of excess) ... special management industrial waste with PCB blend

We handle as PCB mixture no (level of polychlorinated biphenyl: lower than 0.5 mg/kg) ... industrial waste

About judgment of PCB waste

The abolished heavy electric machinery apparatuses concerned not corresponding to PCB waste when levels of polychlorinated biphenyl in insulating oil enclosed in the abolished heavy electric machinery apparatuses which measured for each apparatus about abolished heavy electric machinery apparatuses concerned are 0.5 mg/kg that is aim standard of processing or less. "From ring abolished product No. 040217005"

About disposal of PCB waste

You must consign disposal whether PCB waste works by oneself by March 31, 2027. "The PCB special measures law July 15, 2001 enforcement"

Flow until sample collection and report of PCB analysis

  • 1

    In customers
    Collection of insulating oil

    Such as transformer, condenser
    Insulating oil

    ※We will carry out collection of insulating oil by request.

  • 2

    Preprocessing process

  • 3

    Analysis process

    GC-ECD

  • 4

    Result report

    The detection lower limit level: 0.15 mg/kg

  • saiyu set

    Please consult about saiyuhoho

  • Pre-treatment equipment

  • Gas chromatograph
    Electronic capture type detector (GC-ECD)

Method for measurement

Simple assay manual 2.1.2 about a very small amount of PCB in insulating oil

Heating multi-layer silica gel column/alumina column/kyapitarigasukuromatogurafu/electronic capture type detector (GC/ECD) law (May, 2011 Ministry of the Environment Minister's Secretariat waste, recycling measures part industrial waste section)

Measurement proof business registration: Fukuoka No. 72

In occasion of facilities update and destruction, please feel free to contact.

Inquiry about PCB

Customer-adaptive window

KYUHEN Co., Inc. guarantee of quality department guarantee of quality group
Charge: kabatsuta
TEL: 0940-34-3212 FAX: 0940-34-3228
MAIL: hinsyou1@kyuhen.co.jp

Matter which you want to contact in the case of inquiry
  • The equipment name, model, the number of the phases, the production year, manufacturing number

    ※Apparatus judgment becomes early if there are any the main tablet photographs

  • Contact information (company name, department name, full name, phone number)
About order of a very small amount of PCB analysis
Inquiry about estimate, deadline

Electrical Equipment Sales Department
TEL: 092-771-7851

Inquiry about analysis contents

Insulating oil diagnosis group
TEL: 0940-34-3236