About the issue of PCB
We cannot deny possibility of a very small amount of PCB mixture
About storage of transformer
We can just use thing currently using sequentially. In any of the transformer (use of PCB transformer, transformer that a very small amount of PCB mixture was confirmed) that used apparatus contains PCB, you have Manager Director Ministry of Economy, Trade and Industry atomic energy, NISA industry preservation report by electric report rule based on "Electricity Enterprises Law" concerned, and you follow so that malfunction such as leak oil does not occur, and please carry out check every day.
In addition, it is forbidden using newly when PCB component dismantles confirmed apparatus from electric circuit.
When you remove transformer that mixture of use of PCB transformer, very small amount PCB was confirmed from electric circuit and keep, please follow as follows. In addition, it is necessary appropriate to handle that it followed as follows when we keep thing which cannot deny possibility of PCB mixture.
("2: Paragraph 2 of Article 12 method of waste disposal" ": 13 of Article 8, 2 Paragraph 3 of 2 of Article 8 the method of waste disposal enforcement regulations" ": Ministry of International Trade and Industry Machinery and Information Industries Bureau electric apparatus section in July, 2000 about the handling of use of PCB electric apparatus")
When we keep, we follow method of waste disposal, and I would like the handling according to the next instructions.
1) Identifiably display
We display next and distinguish from general apparatus
Indication (indication of being apparatus which or cannot deny possibility of a very small amount of PCB mixture) of being apparatus that use of PCB, a very small amount of PCB mixture were confirmed
- Amount (the number, mass, capacity)
- Indication (full name, contact information) of administrator
- The year when we started storage
- Processing completion time limit [we show we handle by) in the case of (low concentration PCB waste on March 31, 2027]
- Reference (contact information such as maker names) of apparatus
- As for the thing which handled legal procedure of "method of waste disposal" "Electricity Enterprises Law" either, it is displayed it
2) Isolation of apparatus
We isolate so that we distinguish target apparatus from general, disposing, and insulating oil in the apparatus concerned is scattered and flows out and penetrates underground and bad smell does not display and keep. In addition, we establish partition so that other than manager for storage and manager cannot approach apparatus.
3) Measures of leak oil prevention
When it is to thing keeping, we receive in strong container produced with storing to container which we sealed up, materials which are hard to penetrate and prevent leak caused by corrosion from getting up.
4) Measures of fire prevention
When we keep designated amount (as for the fourth kind third oil 2,000 liters) or more insulating oil, we obey technical standards such as position, structure, facilities of storage area according to the Fire Services Act.
5) Check
We check apparatus keeping regularly and try for prevention such as pollution or loss by leaks. In addition, record check result; together of apparatus keep until disposing is completed.
6) Others
When we dispose, we provide information about property, quantity of contents in trust and dispose by processing technology authorized legally.
1) In the case of transformer with apparatus that a very small amount of PCB mixture was confirmed and the possibility
When we maintain, we would like the handling such as electric insulating oil used for apparatus as follows.
- Oil which we pulled out by oil exchange work can enter container which we sealed up and keeps along Paragraph 1.2 mentioned above.
- We record consumption, maker, standard of oil, work day that oiled, and oil which we supplemented newly keeps. In addition, oil to supplement newly obtains PCB-free certificate from oil manufacturer beforehand.
- We keep tools for appliance, waste, rubber gloves which we used for extraction work of oil and polluted protection along Paragraph 1.2 mentioned above. In addition, we treat about case to include oil which we pulled out for investigation equally.
2) In the case of use of PCB transformer
Please do not perform oil exchange work to make nonproliferation and detoxification handling of pollution difficult.
About the related law
The handling that followed law that is currently using and stop planned electric apparatus warns use enough in application (regulation) of law varying according to the situation of transformer and is related, please.
When a very small amount of PCB mixture transformer is confirmed use of PCB transformer, law ※3 ※Report according to 4 is necessary. When apparatus currently using is available continuously, but remove from electric circuit once, newly to electric circuit cannot be connected (※ 5).
In addition, about highly-concentrated use of PCB electricity workpiece and PCB waste, deadline for disposal every area of notification (prohibition of provisional measure of continuously using, disposal in period) is announced, and disposal in period when we followed law (※ 1 ※ 3 ※ 5) is necessary.
Please see new regulation "of use of PCB electricity workpiece of" high density.
When a very small amount of PCB mixture is not confirmed, we do not receive application of law (※ 3) and can handle (0.5 mg/kg or less) as industrial waste at the time of the disposal.
In addition, about apparatus said to that we cannot completely deny possibility of PCB mixture, processing that is appropriate like PCB waste is necessary till it is confirmed not to contain PCB.
The related law
※1.2 Paragraph 2 of "law about disposal of waste and cleaning" (revision last on June 14, 2019) Article 12
※2.13 of 2 Paragraph 3 Article 8 of 2 of "law enforcement regulations about disposal of waste and cleaning" (revision last on September 4, 2019) Article 8
※3."Special measures law about promotion of appropriate measures of polychlorinated biphenyl waste" (revision last on May 2, 2016) Article 8, Article 10
※4.Paragraph 2 of "electric report rule concerned" (revision last on July 1, 2019) Article 4
※5."Departmental order to determine technical standard about electric equipment" (revision last on March 31, 2017) Chapter 1 basic rule Section 4 (prevention such as pollution) Article 19 14, supplementary provisions Paragraph 2